This is the EMSD Code of Practice reduced to one printable sheet. Print it, laminate it, and keep it in the plant room next to the tower's logbook: the three Legionella action bands, the recurring duties, and a JAN–DEC tick grid for the year's records. The full explanations — with sources — live in the articles linked at the bottom.
System under control. Maintain quarterly monitoring and keep the water treatment programme running.
Investigate and review the treatment programme. Immediate on-line disinfection, then resample within 3–7 days. On an EMSD sample, this band draws an advisory letter.
Immediate emergency decontamination, then resample within 3 days. On an EMSD sample, this triggers a statutory nuisance notice — failing to comply is an offence.
| Duty 項目 | Minimum 最低要求 | Done 完成 |
|---|---|---|
| Cleaning, desludging & disinfection 清洗、除泥及消毒 | At least every 6 months 每六個月至少一次 | 1st 2nd |
| Operation records 每月運行紀錄 | Monthly 每月 | Tick each month in the grid below 於下表逐月打勾 |
| Water quality monitoring — Legionella & HCC 水質監測 | Per the Code — quarterly while under control 受控時每季一次 | Q1 Q2 Q3 Q4 |
| Record retention 紀錄保存兩年 | At least 2 years, readily available 最少兩年,隨時備查 | Filed 已存檔 |
| DUTY 項目 | JAN | FEB | MAR | APR | MAY | JUN | JUL | AUG | SEP | OCT | NOV | DEC |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Operation record completed 運行紀錄 | ||||||||||||
| Water sample taken — Legionella & HCC 水質取樣 | ||||||||||||
| Cleaning & disinfection done 清洗消毒 |
Tick when done and recorded 完成並記錄後打勾 · Samples at least quarterly 取樣每季至少一次 · Cleaning at least every 6 months 清洗每六個月至少一次 · Keep all records 2 years 紀錄保存兩年
EMSD has sampled fresh water cooling towers at random since 2011 — inspections come without notice. 機電工程署自2011年起隨機抽樣,事前不作通知。
Gotech Chemical — cooling tower treatment, cleaning and emergency decontamination since 1982. Phone & WhatsApp, Mon–Sat 9:00–18:00. We reply within one working day. 我們會在一個工作天內回覆。
This sheet condenses two longer guides on this site: the EMSD Code of Practice, in plain English — the water quality table, the full action ladder and the record rules — and cooling tower rules, in plain language, the short version with the enforcement side. If a result has already come back high, go straight to the emergency page.
Yes — this page is designed to print on one to two A4 pages. Use the print button or your browser's print function, then laminate the sheet and keep it in the plant room with the tower's logbook.
Operation and maintenance manuals and records, kept by authorised personnel, readily available for inspection and kept for at least 2 years — including monthly operation records, water quality results, and evidence of cleaning, desludging and disinfection at least every 6 months. Inspections also look for completed checklists, records and logbook covering the past 1 year.
Three bands. Below 10 cfu/mL counts as not detected — keep quarterly monitoring and the treatment programme running. From 10 to under 1,000 cfu/mL, investigate, review the programme, carry out immediate on-line disinfection and resample within 3–7 days; on an EMSD sample this band draws an advisory letter. At 1,000 cfu/mL or above, carry out immediate emergency decontamination and resample within 3 days; on an EMSD sample this triggers a statutory nuisance notice, and failing to comply is an offence.
We run the programme, do the cleaning, take the samples and hand you the dated reports — the whole sheet, done.