Failed a Legionella test? Got an EMSD notice?
Call us now. We handle high Legionella counts and statutory notices regularly, and we know exactly what the EMSD requires next.
Call us now. We handle high Legionella counts and statutory notices regularly, and we know exactly what the EMSD requires next.
If your cooling tower result is at or above 1,000 cfu/mL, or you have received an EMSD nuisance notice: do not drain or dose the system, keep the lab report, and call a specialist contractor now. Emergency decontamination and re-testing are required, and the notice carries a statutory deadline.
If your cooling tower result is at or above 1,000 cfu/mL, an EMSD nuisance notice requires emergency decontamination and re-testing. This is time-critical. Talk to a specialist before you do anything else.
Phone answered Mon–Sat, 9:00–18:00 · WhatsApp any time — mark your message URGENT.
Do not drain or dose the system before taking advice — you can destroy the evidence you will need and make the re-test harder to interpret. Keep the lab report. Note the sample date and location. Then call us. A high result requires cleaning, disinfection and a re-test that demonstrates the count has come down, and all of it has to be documented.
Keep the lab report, do not drain or dose the system, isolate the tower only as advised, and call a specialist contractor. Then: an emergency decontamination visit, a laboratory re-test, and documentation for the file.
In our experience it is rarely “no biocide”. It is more often one of these:
A clean without a diagnosis buys you a few months. The count comes back because the cause never left.
Since 2011 the EMSD has been able to enter premises and sample fresh water cooling towers at random. A total Legionella count at or above 1,000 cfu/mL triggers a statutory nuisance notice requiring emergency decontamination with re-testing. Non-compliance is an offence.
The responsibility sits with the building owner and duty holder — hiring a contractor does not transfer it. What closes a notice is properly executed work plus documents that prove it. See compliance.
Do not drain or dose the system before taking advice — you can destroy evidence and make the re-test harder to interpret. Keep the lab report, note the sample date and location, and call a water treatment specialist. A high count requires cleaning, disinfection and a documented re-test showing the count has come down.
A total Legionella count at or above 1,000 cfu/mL triggers a statutory nuisance notice requiring emergency decontamination with re-testing under the Code of Practice for Fresh Water Cooling Towers. Non-compliance is an offence, and responsibility remains with the building owner and duty holder.
Keep the lab report, do not drain or dose the system, isolate the tower only as advised, and call a specialist contractor. Then: an emergency decontamination visit, a laboratory re-test, and documentation for the file.
Usually because biofilm and sludge shield the organism from biocide, because pH has drifted (chlorine at pH 9 is about 95% in its weak hypochlorite form), or because dosing equipment failed unnoticed between visits.

On a desktop? Scan to WhatsApp us — mark it URGENT.
Call us and we will tell you what the result actually means and what has to happen next.